H07 RN-F


COMMON APPLICATIONS
For all power connexions and mobile installations, indoor or outdoor and unprotected
TECHNICAL CARACTERISTICS
Core : Classe 5 copper according to IEC 60228
Insulation : Vulcanized rubber
Sheath : Non-metallic polychloroprene
Bending radius : 5xD
ELECTRICAL PROPERTIES
Nominal voltage in protected and fixed installations : Uo/U : 0,6/1 kV
Nominal voltage : Uo/U : 450/750 V
Trial voltage : 2.5 kV
Temperature of use : -25 à +55°C
Core temperature : 60°C
CERTIFICATION
Non-propagating flame according to IEC 60332-1
Flame retardant according toVDE0482-332-12/IEC60332-1-2
Oil-resistant according to EN 60811-404
UV resistance: Good
Ozone resistant
PACKAGING
Wooden reel, plastic or cords collar
CONNECTION
Tubular copper connector type CT 20-130 MTR
COMPLIANCE
Classe II mecanical - double insulation
Classe II electrical up to 375V between phase
SECTION DETAILS
SINGLE-CONDUCTOR
Réf | Section (mm²) | Diam ext (mm) | Poids (kg/km) | Intensité Adm 30°C (A) |
|---|---|---|---|---|
H07 RN-F | 1x150 | 25,6 | 1900 | 300 |
H07 RN-F | 1x185 | 27,9 | 2300 | 341 |
H07 RN-F | 1x240 | 31 | 2900 | 407 |
H07 RN-F | 1x300 | 34,1 | 3600 | 468 |
H07 RN-F | 1x400 | 38,5 | 4800 | 553 |
H07 RN-F | 1x500 | 43,5 | 5431 | 634 |
H07 RN-F | 1x630 | 48,5 | 6849 | 742 |
MULTI-CONDUCTOR
Réf | Section (mm2) | Diam Ext (mm) | Poids Câble (Kg/Km) | Intensité Adm 30°C (A) |
|---|---|---|---|---|
H07 RN-F | 3X25 | 27 | 1250 | 89 |
H07 RN-F | 4G25 | 29.3 | 1850 | 92 |
H07 RN-F | 4X25 | 29.3 | 1850 | 92 |
H07 RN-F | 5G25 | 32.5 | 2200 | 94 |
H07 RN-F | 3G35 | 29.6 | 1850 | 135 |
H07 RN-F | 3X35 | 29.6 | 1733 | 110 |
H07 RN-F | 4G35 | 33 | 2310 | 114 |
H07 RN-F | 5G35 | 38 | 2700 | 117 |
H07 RN-F | 3G50 | 36 | 3790 | 169 |
H07 RN-F | 4G50 | 38.2 | 3160 | 143 |
H07 RN-F | 5G50 | 44.5 | 3950 | 148 |
H07 RN-F | 4G70 | 43.2 | 4250 | 178 |
.png)